4.37 Regulation of Occupational Safety and Health Regulations 1996, an obligation on a person who is an employer, a builder, a self-employed person, one person at a workplace or a person who has access to a workplace in order to" ensure that the plant is at work on an appropriate controls, checks and controls are necessary to reduce the risk of injury or damage caused to a person at work.
An electrical testing and tagging system for electrical appliances is the way to ensure compliance with the above regulation.
The following licenses shall be subject to the examination of electrical equipment and installations in other businesses as construction sites:
Electrical Testing using a plug-in tester:
In the examination by inserting into a commercially available "plug-in" test-PAT device, the person performing the tests do not need any electrical license and can be the appropriate day. Note that if the device is found to be defective, it can only be repaired by an appropriately licensed electrician.
Electrical testing of electrical test instruments:
Where testing is done with an instrument, with hand probes or clip-on leads, such as an insulation resistance meter and the equipment to be partially dismantled, then the person responsible for the examination must be at least an "A" grade electrical mechanic or electrical fitter's license or a restricted electrical license with the "scope of work required for the type of equipment tested.
Sites
Regulation 3.61 of the Occupational Safety and Health Regulations 1996 specifies that electrical equipment, appliances and equipment on construction sites must comply with the Australian New Zealand Standard AS / NZS 3012 "Electrical installations - Construction and demolition waste sites." Clause 3.6 of AS / NZS 3012:2003 specifies that electrical equipment be tested and in accordance with AS / NZS 3760 "In-service safety inspection and testing of electrical equipment." Regulation 3.62 of the Occupational Safety and Health Regulations 1996 requires that persons who test and license number on the tag must be electrical workers within the meaning of the Electricity (Licensing) Regulations, the 1991st The electrical worker must be the holder of either an "A" grade electrical mechanic or electrical fitter's license or a restricted electrical license with the "scope of work required for the type of equipment tested.
Pits
Regulation 5.27 of the Mines Safety and Inspection Regulations 1995, that the portable devices, which are usually severe operating environments must be examined, tested and tagged every three months. The electrical licensing requirements for persons who conduct the examination on pits are the same as for "jobs than other sites" before. In all cases, if the equipment or appliance requires disassembly or repair, only the owner of an electrical or electro-mechanic mechanic's license or a restricted electrical license with the "scope of work required for the type of equipment will be dismantled can be repaired or carry out the necessary electrical work.
Advice to employees
Electrical testing and labeling of all portable devices such as AS3760 should now be the norm in all workplaces. If this is not the case in your workplace, you as an employee and your employer should require that as soon as possible. If it does not happen, then the employer against his / her duty under Regulation 4.37 of the Occupational Safety
All Safe Test and day is your No. 1 for all electrical testing and tagging queries. We at all sure that the goal of only factual information about the AS3760 and portable appliance testing to ensure that you are fully aware that you are in the workplace a safer environment.